CA3-B0-22-640-12A-C [Carling Technologies]
Magnetic Circuit Breaker,;型号: | CA3-B0-22-640-12A-C |
厂家: | Carling Technologies |
描述: | Magnetic Circuit Breaker, |
文件: | 总26页 (文件大小:2748K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
C-
riesSeries
C-Se
CIRCUIT BREAKER
The C-Series hydraulic-magnetic circuit breakers are ideal for applications that require higher amperage and
voltage handling capability in a smaller package. They are available in 1-6 poles, 0.02-100amps, UL Recognized
up to 480VAC or 150VDC, UL489 Listed up to 240VAC or 125VDC, with choice of time delays, terminal
options, actuator styles and colors. The C-Series employs a unique arc chute design which allows for higher
interrupting capacities of up to 10,000 amps. New thermoset glass filled polyester half shell construction
provides for increased mechanical and electrical strength. The wiping contacts, mechanical linkage with two
step actuation, clean contacts providing high, positive contact pressure and longer contact life. Available with
American Standard or Metric Threaded Stud terminals, or Saddle Clamp screw terminals. The optional mid-trip
handle style actuator allows a visual indication of electrical overload with or without alarm feature.
Product Highlights:
Extensive list of Agency Approvals
Typical Applications:
Marine
Available with Standard or Metric Stud terminals,
Telecom/Datacom
Military
Renewable Energy
Generators & Welders
or Saddle Clamp screw terminals
Optional mid-trip handle style actuator
Unique arc chute design which allows for higher
interrupting capacities of up to 10,000 amps
Exclusive Rockerguard and Push-To-Reset bezel
Available with new solid color and two-color Visi-
rocker® actuators
New thermoset glass filled polyester half shell
construction
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Email: sales@carlingtech.com
Application Support: team2@carlingtech.com
Phone: 860.793.9281 Fax: 860.793.9231
www.carlingtech.com
|
C-Series Circuit Breaker - General Specifications
2
Electrical
Maximum Voltage
Mechanical
Endurance
AC, 480 WYE/277 VAC, 50/60 Hz
(see Table A.)
UL489: AC,240 VAC. (See Table D),
50/60 Hz, 125 VDC
Standard current coils: 0.100,
0.250, 0.500, 0.750, 1.00, 2.50,
5.00, 7.50, 10.0, 15.0, 25.0, 30.0,
35.0, 40.0, 50.0, 60.0, 70.0, 80.0,
90.0 and 100 amps. Other ratings
available, see Ordering Scheme.
10,000 ON-OFF operations @ 6 per
minute; with rated current &
voltage.
Trip Free
All C-Series circuit breakers will trip
on overload, even when actuator is
forcibly held in the ON position.
The operating actuator moves
positively to the OFF position when
an overload causes the breaker to
trip. With mid-trip, handle moves to
the mid position on electrical trip of
the circuit breaker. With mid trip
handle with alarm switch, handle
moves to the mid position and the
alarm switch actuates when the
circuit breaker is electrically
tripped.
Current Rating
Trip Indication
Standard Voltage Coils DC - 6V, 12V; AC - 120V; other
ratings available, see Ordering
Scheme.
Auxiliary Switch Rating SPDT; 10.1 amps-250VAC, DC Aux.
Switch 1.0A, 65 VDC. 0.5A,
80VDC,1/4 HP, 125VAC,VDE & TUV
1.0 125 VAC.
Insulation Resistance
Dielectric Strength
Minimum of 100 Megohms at 500
VDC.
Physical
UL, CSA: 1960 V 50/60 Hz for one
minute between all electrically
isolated terminals. C-Series Circuit
Breakers comply with the 8mm
spacing and 3750V 50/60 Hz
dielectric requirements from
hazardous voltage to operator
accessible surfaces, between
adjacent poles and from main
circuits to auxiliary circuits per
Publications EN 60950 and
VDE 0805.
Number of Poles
1-6 poles ≤ 50A; 1-4 poles @ 51-
70A; 1-2 poles 71-100A. UL489
Handle: 1 pole ≤ 100A, 2 pole ≤
50A; Rocker: 1 pole ≤ 100A.
Internal Circuit Config. Series (with or without auxiliary
switch, mid trip & mid trip with
alarm switch) Shunt & Relay with
current or voltage trip coils, Dual
Coil, Switch Only (with or without
aux. switch). UL489: Series (with or
without auxiliary switch, mid-trip &
midtrip with alarm switch).
Resistance, Impedance Values from Line to Load Terminal -
based on Series Trip Circuit
Weight
Standard Colors
Approx.112 grams/pole ( 3.95 oz).
Housing: Black
RESISTANCE, IMPEDANCE VALUES
Breaker.
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
Environmental
1000
CURRENT
(AMPS)
TOLERANCE
(%)
Designed and tested in accordance with requirements of
100
10
specification MIL-PRF-55629 & MIL-STD-202 as follows:
0.10 - 5.0
5.1 - 20.0
20.1 - 50.0
15
25
35
Shock
Withstands 100 Gs, 6ms sawtooth
while carrying rated current per
Method 213, Test Condition “I”.
Instantaneous and ultrashort curves
tested @ 90% of rated current.
Withstands 0.060” excursion from
10-55 Hz & 10 Gs 55-500 Hz, @
rated current per Method 204C,
Test Cond. A. Instantaneous &
ultrashort curves tested @ 90% of
rated current.
Method 106D, i.e., ten 24-hour
cycles @ +25°C to +65°C,
80-98% RH.
Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Method 107D, Condition A (five
cycles @ -55°C to +25°C to +85°C
to +25°C).
O
H
M
S
1
0.1
0.01
Vibration
0.001
0.01
0.1
1
10
100
AMPERE RATING
Pulse Tolerance Curves
60 Hz 1/2 Cycle
Inrush Pulse Tolerance
50 Hz 1/2 Cycle
Moisture Resistance
Inrush Pulse Tolerance
I
I
r
r
Time Delay Curves
Time Delay Curves
42, 44
& 46
22x
10x
42, 44
& 46
(50 Amps Max.)
(50 Amps Max.)
25x
12x
Time Delay Curves
Time Delay Curves
22, 24 (100 Amps Max.)
26 (70 Amps Max.)
22, 24 (100 Amps Max.)
26 (70 Amps Max.)
Salt Spray
t
t
10.0
20.0
5.0
8.33
16.67
4.165
Time in
Milliseconds
Thermal Shock
Operating Temperature -40°C to +85°C
*Manufacturer reserves the right to change product specification without prior notice.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
C-Series Circuit Breaker - General Specifications |
3
Electrical Tables
Table A: Lists UL Recognized & CSA Accepted configurations and performance capabilities as a Component Supplementary
Protector
C-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTORS
SHORT CIRCUIT CAPACITY (AMPS)
VOLTAGE
CURRENT RATING
APPLICATION CODES
UL/CSA
CIRCUIT
CONFIGURATION
NOTES
WITH BACKUP
FUSE 1
MAX.
RATING
FULL LOAD
AMPS
GENERAL
PURPOSE AMPS
WITHOUT BACKUP
FREQUENCY PHASE
UL
CSA
FUSE
32
48
65
DC
DC
DC
---
---
---
0.02 - 100
110 - 150
0.02 - 70
---
---
---
---
---
---
---
---
---
---
5000
5000
5000
5000
7500
7500
10,000
10,000
5000
5000
5000
3000
5000
5000
5000
3500
3000
1000
5000
3500
5000
---
TC1, OL1, U2
TC1, OL1, U2
TC1, OL1, U2
TC1, OL1, U2
---
---
TC1,2, OL1,U1 TC1,2, OL1,U1
TC1,2, OL0,U1 TC1,2, OL0,U1
TC1,2, OL1,U1 TC1,2, OL1,U1
TC1,2, OL0,U1 TC1,2, OL0,U1
TC1,2, OL1,U1 TC1,2, OL1,U1
TC1,2, OL0,U1 TC1,2, OL0,U1
71 -100
0.02 - 70
---
---
80
80
DC
DC
---
---
71 -100
0.02 - 70
---
---
Must Have Agency Code "L"
Must Have Agency Code "L"
71 -100
125
125 / 250
250
DC
DC
DC
---
---
---
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 100
0.02 - 100
---
---
TC1,2,OL1,U1
TC1,2,OL1,U1
TC1,2,OL1,U1
TC1, OL1, U2
TC1,2,OL1,U1
TC1, OL0, U3
TC1, OL0, U3
TC1, OL1, U2
TC1,2,OL1,U1
TC1,2,OL1,U1
TC1,2,OL1,U2
TC1, OL1, U2
TC1,2,OL1,U1
TC1,2,OL1,C1
TC1, OL0, U2
TC1,2,OL1,C1
TC1,2,OL0,U1
TC1,2,OL1,C1
TC1,2,OL1,C1
TC1,2,OL0,C1
TC1,2,OL1,C1
TC1,2,OL0,C1
TC1,2,OL1,U1
TC1,2,OL1,U1
TC1,2,OL1,U1
TC1, OL1, U2
TC1,2,OL1,U1
---
Must Have Agency Code "L"
---
Must Have Agency Code "L"
---
Must Have Agency Code "L". 2 Pole Break Required for 250 Volts
Per Pole Rating
---
---
---
125
50 / 60
1
---
Must Have Agency Code "L"
150
150
DC
DC
---
---
80 - 100
---
Must Have Agency Code "L"
---
101 - 175
---
---
Must Have Agency Code "L" Parallel Pole
SERIES
0.02 - 100
0.02 - 50
51 - 100
0.02 - 100
0.02 - 50
0.02 - 100
51 - 70
---
---
---
TC1, OL1, U2
TC1,2,OL1,U1
TC1,2,OL1,U1
TC1,2,OL1,U2
TC1, OL1, U2
TC1,2,OL1,U1
TC1,2,OL1,C1
TC1, OL0, U2
TC1,2,OL1,C1
TC1,2,OL0,U1
TC1,2,OL1,C1
TC1,2,OL1,C1
TC1,2,OL0,C1
TC1,2,OL1,C1
TC1,2,OL0,C1
---
---
2 or 3 poles breaking single phase
2 or 3 poles breaking single phase
2 or 3 poles breaking single phase, "L" Agency Code
Per Pole Rating
125 / 250
50 / 60
1
---
---
---
---
---
---
1
3
---
---
Must Have Agency Code "L"
---
5000
---
250
50 / 60
0.02 - 100
3000
---
0.02 - 70
---
---
0.02 - 90
---
5000
---
3 poles breaking 3 phase
5000
---
Must Have Agency Code "L"
277
50 / 60
50 / 60
1
3
0.02 - 50
0.02 - 30
---
5000
5000
5000
5000
5000
---
---
---
3 poles breaking 3 phase
2 poles breaking 1 phase
480 / 277
31 - 50
---
---
0.02 - 30
---
---
480
50 / 60
1
31 - 50
---
---
80
DC
---
1
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 30
---
7500
3000
3500
3000
3500
3000
---
TC1,2, OL1,U1 TC1,2, OL1,U1
125
50 / 60
---
---
TC1, OL1, U2
TC1, OL1, U2
TC1,2,OL1,U1
TC1, OL1, U2
TC1, OL0, U2
TC1,2,OL1,C1
TC1,2,OL1,C1
TC1, OL1, U2
TC1, OL1, U2
TC1,2,OL1,U1
TC1, OL1, U2
TC1, OL0, U2
TC1,2,OL1,C1
TC1,2,OL1,C1
Per Pole Rating
---
---
2 or 3 poles breaking single phase
2 or 3 poles breaking single phase
125 / 250
50 / 60
1
1
3
---
---
DUAL COIL
---
---
250
50 / 60
---
---
Per Pole Rating
---
5000
5000
---
277
80
50 / 60
DC
1
---
1
---
---
3 poles breaking 3 phase
---
7500
---
TC1,2, OL1,U1 TC1,2, OL1,U1
277
250
50 / 60
50 / 60
---
5000
5000
5000
5000
5000
5000
---
TC1,2,OL1,C1
TC1,2,OL1,C1
TC1,2,OL1,C1
TC1,2,OL0,C1
TC1,2,OL1,C1
TC1,2,OL0,C1
TC1,2,OL1,C1
TC1,2,OL1,C1
TC1,2,OL1,C1
TC1,2,OL0,C1
TC1,2,OL1,C1
TC1,2,OL0,C1
3
---
---
3 poles breaking 3 phase
3 poles breaking 3 phase
SHUNT
RELAY
---
---
480 / 277
480
50 / 60
50 / 60
3
1
31 - 50
---
---
0.02 - 30
---
---
2 poles breaking 1 phase
31 - 50
---
---
80
DC
---
1
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 70
---
7500
---
TC1,2, OL1,U1 TC1,2, OL1,U1
277
250
50 / 60
50 / 60
---
5000
5000
---
TC1,2,OL1,C1
TC1,2,OL1,C1
3
---
---
TC1,2,OL1,C1
TC1,2,OL1,C1
3 poles breaking 3 phase
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
65
80
DC
DC
---
---
71 -100
---
---
---
0.02 - 70
---
---
---
71 -100
---
---
---
125
50 / 60
50 / 60
1
1
1
3
1
0.02 - 100
0.02 - 100
0.02 - 100
0.02 - 70
0.02 - 50
0.02 - 30
---
---
---
SWITCH ONLY
125 / 250
---
---
---
2 or 3 poles breaking single phase
3 poles breaking 3 phase
---
---
---
250
277
50 / 60
50 / 60
50 / 60
---
---
---
---
---
---
---
---
---
480 / 277
3
31 - 50
---
---
Notes:
1.
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less
rating and not to exceed 175 for 51 through 100 Amp rating
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
4
C-Series Circuit Breaker - General Specifications
Electrical Tables
Table B: Lists UL Recognized and CSA Accepted configurations and performance capabilities as a Manual Motor Controller.
RELAY
Notes:
1
UL recognized and CSA Accepted at 480V refers to 3 & 4 pole versions used in a 3Ø, wye connected circuit or 2-pole version connected with 2 poles breaking. 1Ø and backed up with
series fusing as stated above in note 1.
*
Series, Shunt and Relay Trip - Voltage Coil Construction not current coils
Table C: Lists UL Recognized, CSA Accepted, VDE and TUV Certified configurations and performance capabilities as a
Component Supplementary Protector.
Notes:
1.
2.
General Purpose ratings for UL/CSA only.
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less
rating and not to exceed 175 for 51 through 100 Amp rating.
Table D: Lists UL Listed (489), CSA Certified (C22.2 No. 5.1-M) configuration and performance capabilities as a Molded Case
Circuit Breaker.
C SERIES TABLE D : UL489 LISTED BRANCH CIRCUIT BREAKERS
INTERRUPTING
CAPACITY
(AMPS)
CURRENT
RATING
VOLTAGE
FREQUENCY
DC
CIRCUIT
CONFIGURATION
CONSTRUCTION NOTES
MAX.
RATING
FULL LOAD
AMPS
WITHOUT
BACKUP FUSE
PHASE
---
50,0001
10,000
Limited to 2 Poles Max from 71 - 100 Amps.
80
0.10 - 100
Limited to 2 Poles Max from 71 - 100 Amps.
125
DC
DC
---
---
0.10 - 100
0.10 - 50
0.10 - 50
51 - 70
5,000
5,000
1 - 3 Poles
125 / 250
1 or 2 Poles (2 Poles Required for 250 Volts)
10,000
5,000
1 - 3 Poles
120
50 / 60
50 / 60
1
1
SERIES
1 - 3 Poles
0.10 - 50
5,000
2 or 3 Poles. 1 Pole of a 3 Pole Unit is Neutral
120 / 240
100001
5,000
2 or 3 Poles. 1 Pole of a 3 Pole Unit is Neutral
0.10 - 50
0.10 - 30
0.10 - 20
0.10 - 20
0.10 - 30
240
240
277
120
50 / 60
50 / 60
50 / 60
50 / 60
1
1
1
1
1Pole
2 Pole
1Pole
---
5,000
10,000
10,000
DUAL COIL
Notes from Table D:
1.
Special catalog number required. Consult factory.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
C-Series Circuit Breaker - General Specifications |
5
Electrical Tables
Table E: Lists UL Recognized, CSA Accepted configurations and performance capabilities as Protectors, Supplementary for
Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classified Small Craft
Electrical Devices, Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors.
Table F: Lists UL Listed configurations and performance capabilities as Circuit Breakers for use in Communications Equipment
(Guide DITT, File E189195), under UL489A.
Agency Certifications
Component Supplementary
Protector under Class 3215 30,
FIle 047848 0 000 CSA
UL Recognized
UL Standard 1077
CSA Accepted
Component Recognition Program
as Protectors Supplementary
(Guide CCN/QVNU2, File E75596)
Standard C22.2 No. 235
Switches, Industrial Control
(Guide CCN/NRNT2, File E148683)
Circuit Breaker Model Case
(Class 1432 01, File 093910),
CSA Standard C22.2 No. 5.1 - M
UL Standard 508
UL Standard 1500
CSA Certified
TUV Certified
VDE Certified
Protectors, Supplementary for
Marine Electrical & Fuel Systems
(Guide PEQZ2, File E75596)
Ignition Protection
EN60934, under License No.
R72040875
UL Listed
UL Standard 489
Circuit Breakers, Molded Case,
(Guide DIVQ, File E129899)
EN60934, VDE 0642 under File
No. 10537
Communications Equipment
UL Standard 489A
(Guide CCN/DITT, File E189195)
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
6
C-Series Circuit Breaker - Handle UL Recognized – Ordering Scheme
C A 3 B 0 10 450 1 2 1 C
8
9
10
11
Agency
Approval
1
2
3
4
5
6
7
Terminal
Actuator
Color
Mounting
Bezel/Barrier
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
1 SERIES
C
7 CURRENT RATING (AMPERES)
CODE AMPERES
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
1
2 ACTUATOR
A
B
S
T
Handle, one per pole
Handle, one per multipole unit
Mid-Trip Handle, one per pole
Mid-Trip Handle, one per pole & Alarm Switch
2
3 POLES
1
2
One
Two
3
4
Three
Four
5
6
Five
Six
9
660 60.000
9
670 70.000
3
4
4
4,5
4 CIRCUIT
F
G
H
Relay Trip (Current)
Relay Trip (Voltage)
Dual Coil with Shunt Trip
Voltage Coil
Dual Coil with Relay Trip
Voltage Coil
9
680 80.000
3
A
B
C
D
E
Switch Only (No Coil)
Series Trip (Current)
Series Trip (Voltage)
Shunt Trip (Current)
Shunt Trip (Voltage)
9
685 85.000
9
690 90.000
9
695 95.000
4
4
4,5
K
9
810 100.00
7
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)
CODE AMPERES
5 AUXILIARY / ALARM SWITCH
A06
6 DC
A32 32 DC
A48 48 DC
A65 65 DC
J12 12 AC
J18 18 AC
J24 24 AC
J48 48 AC
J65
65 AC
0
2
3
4
without Aux Switch
A12 12 DC
A18 18 DC
A24 24 DC
K20 120 AC
L40 240 AC
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
J06
6 AC
15
8 TERMINAL
10
12
13,15
15
14
11,15
1
2
3
4
5
Stud 10-32
Screw 10-32
Stud 1/4-20
Stud M5 x 0.8
Screw M5 x 0.8
6
7
9
A
C
Stud M6
11
12
11
11
0.250 Double Click Connect
7/16” Clip Terminal
Plug-In Stud
6 FREQUENCY & DELAY
3
7
03
10
11
12
14
16
20
21
22
24
26
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
30
31
32
34
36
42
44
46
52
54
56
DC 50/60Hz Instantaneous
DC 50/60Hz Ultra Short
DC 50/60Hz Short
DC 50/60Hz Medium
DC 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
5/16” Clip Terminal
16
8
8
8
8
8
9 ACTUATOR COLOR & LEGEND
Actuator Color
White
Black
Red
Green
Blue
Yellow
Gray
7
I-O
A
C
F
H
K
M
P
ON-OFF
Dual
1
Legend Color
Black
White
White
White
White
Black
Black
Black
B
D
G
J
2
3
4
5
6
7
8
9
L
Notes:
N
Q
S
U
1
Actuator Code:
A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units.
B: Handle location as viewed from front of breaker:
Orange
Black (short handle)
R
T
17
White
2 pole - left pole 3 pole - center pole 4 pole - two handles at center poles
5 pole - three handles at center poles
6 pole - four handles at center poles
S: Handle moves to mid-position only upon electrical trip of the breaker. Available
with circuit codes B, C, D, E, F, G, H and K.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip
of the breaker. Available with circuit codes B & C.
Standard multipole units have all poles identical except when specifying auxiliary
switch and/or mixed poles. 4 pole max with VDE. 5th pole available as Series Trip with
Voltage Coil only.
Switch Only circuits, rated up to 50 amps and 6 poles, and only available with VDE
Certificationꢀwhenꢀtiedꢀtoꢀaꢀprotectedꢀpoleꢀ(CircuitꢀCodeꢀB,ꢀC,ꢀDꢀorꢀH.).ꢀForꢀ.02ꢀtoꢀꢀ
30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650.
For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit
Codes D, F, H & K available up to 50 amps maximum Current Rating.
Consult factory for available Dual Coil options, as special catalog number is
required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously
on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip
instantaneously and are rated for intermittent duty only.
10 MOUNTING / BARRIERS
MOUNTING STYLE
BARRIERS
VOLTAGE
2
Threaded Insert
1
6-32 x 0.195 inches
6-32 X 0.195 inches
6-32ꢀXꢀ0.195ꢀinchesꢀꢀ
ISO M3 x 5mm
ISO M3 x 5mm
ISOꢀM3ꢀxꢀ5mmꢀꢀ
no
< 300
< 300
≥ꢀ300
< 300
< 300
≥ꢀ300
A
C
2
B
D
yes
yesꢀꢀ
no
yes
yesꢀꢀ
3
18
18
ꢀ
ꢀ
ꢀ
4
5
Front panel Snap-In, 1.00” [25.4mm] wide bezel
17
E
with Handleguard
no
< 300
6
Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole
breakers, one auxiliary switch is supplied, mounted in the extreme right pole.
Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20.
Available with Circuit Codes B & D only, and up to 50 amps maximum.
Current Ratings 60 - 70 are available up to four poles maximum. Ratings 71 - 100
are available up to two poles maximum.
11 AGENCY APPROVAL
UL Recognized, CSAAccepted
Dꢀ VDEꢀCertified,ꢀULꢀRecognized,ꢀCSAꢀAccepted
Eꢀ TUVꢀCertified,ꢀULꢀRecognized,ꢀCSAꢀAccepted
C
7
8
9
Hꢀ UL489ꢀConstruction:ꢀVDEꢀCertified,ꢀULꢀRecognized,ꢀCSAꢀꢀAccepted
10 Terminal Code 1 available to 60 amps maximum.
11 Terminal Codes 2, 4, 5 and C available to 50 amps maximum.
12 Terminal Codes 3, 6 & 9 available to 100 amps maximum.
13 Terminal Code 7 available to 25 amps maximum.
14 Terminal Code A available to 100 amps maximum.
15 Terminal Codes 7, 9 & C are not VDE approved.
16 No marking available. Consult factory. VDE/TUV Approval requires dual
(I-O, ON-OFF) or I-O markings on all handles.
I
UL Recognized STD 1077, UL Recognized 1500 (ignition protected),
CSAAccepted
L
UL489 Construction: UL Recognized, CSAAccepted
Rꢀ UL489ꢀConstruction:ꢀTUVꢀCertified,ꢀULꢀRecognized,ꢀCSAꢀAccepted
17 Single pole only.
18 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 - 4 poles only
and limited to AC Delays. “General Purpose amps” not rated for “full load amps” or
to be used in applications with a motor.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
C-Series Circuit Breaker - Handle UL489A Listed / Parallel Pole – Ordering Scheme |
7
C A 2 P 0 D4 820 3 2 1 M T
8
9
10
Mounting
11
12
1
2
3
4
5
6
7
Terminal
Actuator
Color
Max. App. Agency
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
Rating
Approval
5
8 TERMINAL
1 SERIES
C
3
6
A
Stud 1/4-20
Stud M6
Plug-In Stud
3
2 ACTUATOR
A
S
T
Handle, one per pole
Mid-Trip Handle, one per pole
Mid-Trip, one per pole & Alarm Switch
2
1
9 ACTUATOR COLOR
1
LEGEND
ON-OFF
B
D
G
J
Dual
Legend Color
Black
White
White
White
White
Black
Black
Black
White
Black
Red
Green
Blue
Yellow
Gray
Orange
1
2
3
4
5
6
7
8
4
3 POLES
One
1
2
Two
3
Three
L
4 CIRCUIT
Series Trip (parallel pole)
N
Q
S
P
5 AUXILIARY / ALARM SWITCH
10 MOUNTING
0
2
3
4
without Aux Switch
6
7
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.110 Q.C
Term. (Gold Contacts)
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
Threaded Insert
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
1
2
6-32 x 0.195 inches
ISO M3 x 5mm
8
9
5
S.P.S.T., N.O., 0.110 Q.C
Term. (Gold Contacts)
11 MAXIMUM APPLICATION RATING
80 DC
M
6 FREQUENCY & DELAY
D1 DC Ultra Short
D2 DC Short
D4 DC Medium
D6 DC Long
6
12 AGENCY APPROVAL
A
Without Approval
Kꢀꢀ
T
UL489AꢀListed,ꢀVDEꢀCertifiedꢀ
UL489A Listed
7ꢀ
UL489AꢀListed,ꢀTUVꢀCertified
4
7 CURRENT RATING (AMPERES)
CODE AMPERES
810 100.00
811 110.00
812 120.00
912 125.00
813 130.00
814 140.00
815 150.00
816 160.00
817 170.00
917 175.00
818 180.00
819 190.00
820 200.00
922 225.00
825 250.00
Notes:
1
Handle moves to Mid-Position only upon electrical trip of C/B when Actuator S is
specified.ꢀWhenꢀActuatorꢀCodeꢀTꢀisꢀspecified,ꢀhandleꢀmovesꢀtoꢀMidꢀPositionꢀandꢀꢀ
Alarm Switch actuates only upon electrical trip of C/B. Code T is only available with
Circuit Code N.
ꢀ
2
3
Standard Handle colors are White, Black, Red & Yellow.
Breakers with Terminal Codes 3 & 6 are supplied with bus bars connecting the Line
and Load Terminals. For Terminal Code A, Line and Load Terminals must be
connected to a copper bus bar having a minimum cross-section of 0.078 square
inches. Terminal code A not available on the single pole unit.
Ratings for 101 to 125 amps are available in 1-pole size.
Ratings from 110 to 200 amps are available in 2-pole size.
For ratings from 225-250 amps, specify 3-pole size.
4
For ratings from 350-400 amps, specify 4-pole size.
5
6
1 pole only available with terminal codes 3 and 6.
Agency codes K and 7 not available with 1 pole.
Agency code J only available with 1 pole.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
8
C-Series Circuit Breaker - Rocker UL489A Listed / Parallel Pole – Ordering Scheme
C 1 2 P 0 D4 820 3 2 A M T
8
9
10
Mounting
11
12
1
2
3
4
5
6
7
Terminal
Actuator
Color
Max. App. Agency
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
Rating
Approval
3
8 TERMINAL
1 SERIES
C
3
6
A
Stud 1/4-20
Stud M6
Plug-In Stud
1
2 ACTUATOR
C
D
F
G
J
K
N
O
1
2
3
4
5
Curved Rocker, Two Color Visi, Indicate On, Vertical Legend
Curved Rocker, Two Color Visi, Indicate On, Horizontal Legend
Curved Rocker, Two Color Visi, Indicate Off, Vertical Legend
Curved Rocker, Two Color Visi, Indicate Off, Horizontal Legend
Curved Rocker, Single Color, Vertical Legend
9 ACTUATOR COLOR
LEGEND
ON-OFF
B
D
G
J
Dual
Legend Color
Black
White
White
White
White
Black
Black
Black
White
Black
Red
Green
Blue
Yellow
Gray
Orange
1
2
3
4
5
6
7
8
Curved Rocker, Single Color, Horizontal Legend
Curved Rocker, Push To Reset, Two Color Visi, Vertical Legend
Curved Rocker, Push To Reset, Two Color Visi, Horizontal Legend
Flat Rocker, Two Color Visi, Vertical Legend
Flat Rocker, Two Color Visi, Horizontal Legend
Flat Rocker, Single Color, Vertical Legend
L
N
Q
S
Flat Rocker, Single Color, Horizontal Legend
Flat Rocker, Push To Reset, Two Color Visi, Vertical Legend
Flat Rocker, Push To Reset, Two Color Visi, Horizontal Legend
Flat Rocker, Push To Reset, Single Color, Vertical Legend
Flat Rocker, Push To Reset, Single Color, Horizontal Legend
6
7
8
10 MOUNTING
ROCKER / MOUNTING INSERT STYLE
Standard Rocker Bezel - 6-32 Inserts
Standard Rocker Bezel - M3 Inserts
Rocker Guard Bezel - 6-32 Inserts
Rocker Guard Bezel - M3 Inserts
Standard Bezel with recessed Off Side Flat Rocker - 6-32 Inserts
Standard Bezel with recessed Off Side Flat Rocker - M3 Inserts
Push to Reset Bezel - 6-32 Inserts
A
B
C
D
E
F
2
3 POLES
One
1
2
Two
3
Three
4 CIRCUIT
Series Trip (parallel pole)
G
H
P
Push to Reset Bezel - M3 Inserts
11 MAXIMUM APPLICATION RATING
80 DC
5 AUXILIARY/ALARM SWITCH
M
0
2
3
4
without Aux Switch
6
7
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.110 Q.C
Term. (Gold Contacts)
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
4
8
9
12 AGENCY APPROVAL
A
T
7ꢀ
Without Approval
UL489A Listed
UL489AꢀListed,ꢀTUVꢀCertified
5
S.P.S.T., N.O., 0.110 Q.C
Term. (Gold Contacts)
Notes:
6 FREQUENCY & DELAY
D1 DC Ultra Short
D2 DC Short
D4 DC Medium
D6 DC Long
1
Breakers with Terminal Codes 3 & 6 are supplied with bus bars connecting the Line
and Load Terminals. For Terminal Code A, Line and Load Terminals must be
connected to a copper bus bar having a minimum cross-section of 0.078 square
inches. Terminal code A not available on the single pole unit.
Ratings for 101 to 125 amps are available in 1-pole size.
Ratings from 110 to 200 amps are available in 2-pole size.
For ratings from 225-250 amps, specify 3-pole size.
2
For ratings from 350-400 amps, specify 4-pole size.
2
3
4
1 pole only available with terminal codes 3 and 6.
Agency codes K and 7 not available with 1 pole.
7 CURRENT RATING (AMPERES)
CODE AMPERES
810 100.00
811 110.00
812 120.00
912 125.00
813 130.00
814 140.00
815 150.00
816 160.00
817 170.00
917 175.00
818 180.00
819 190.00
820 200.00
922 225.00
825 250.00
Agency code J only available with 1 pole.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
C-Series Circuit Breaker - Handle UL489 Listed – Ordering Scheme |
9
C A 3 B 0 14 450 1 2 1 K G
8
9
10
Mounting/
Barriers
11
12
1
2
3
4
5
6
7
Terminal
Actuator
Color
Max. App. Agency
Rating Approval
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
1 SERIES
C
7 CURRENT RATING (AMPERES)
CODE AMPERES
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
660 60.000
670 70.000
680 80.000
685 85.000
690 90.000
695 95.000
810 100.00
1
2 ACTUATOR
A
B
S
T
Handle, one per pole
Handle, one per multipole unit
Mid-Trip Handle, one per pole
Mid-Trip Handle, one per pole & Alarm Switch
2
3 POLES
One
1
2
Two
3
Three
4 CIRCUIT
Series Trip (Current)
B
3
5 AUXILIARY / ALARM SWITCH
0
2
3
4
without Aux Switch
6
8 TERMINAL
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
7
9
9
10
1
2
3
4
5
Stud 10-32
Screw 10-32
Stud 1/4-20
Stud M5 x 0.8
Screw M5 x 0.8
6
9
A
C
Stud M6
7/16” Clip Terminal
Plug-In Stud
5/16” Clip Terminal
8
9
8
8
8
6 FREQUENCY & DELAY
11
12
14
16
21
22
24
DC Ultra Short
DC Short
DC Medium
26
42
44
46
52
54
56
50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
11
9 ACTUATOR COLOR & LEGEND
4
4
4
4
4
4
Actuator Color
White
Black
Red
Green
Blue
Yellow
Gray
Orange
ON-OFF
Dual
Legend Color
Black
White
White
White
White
Black
Black
Black
B
D
G
J
1
2
3
4
5
6
7
8
DC Long
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
L
N
Q
S
Notes:
1
Actuator Code:
A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units.
B: Handle located, as viewed from front of breaker in left pole. 2 pole maximum.
S: Handle moves to mid-position only upon electrical trip of the breaker.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip
of the breaker.
10 MOUNTING / BARRIERS
MOUNTING STYLE
12
BARRIERS
2
ꢀ
Standard multipole units have all poles identical except when specifying auxiliary
switch and/or mixed poles.
2 & 3 pole circuit breakers required for 120/240 VAC (Maximum application rating
code C) applications, have all poles identical except when specifying auxiliary /
alarmꢀswitchꢀwhichꢀisꢀnormallyꢀsuppliedꢀinꢀextremeꢀrightꢀpoleꢀperꢀfigureꢀB.ꢀTerminalꢀꢀ
barriers are required on all multipole breakers.
Threaded Insert
1
2
6-32 x 0.195 inches
ISO M3 x 5mm
yes
yes
Third pole is for 120/240 VAC applications requiring neutral disconnect. The 3rd
pole has the same construction as poles 1 & 2.
On multi-pole breakers, one auxiliary. switch is supplied, mounted in the extreme
right pole.
VDE approval on auxiliary switch codes 2, 3 & 4 only.
Auxiliary / Alarm Switch with Independent Circuit ie: separate from breaker circuit,
only available with circuit breakers rated 50 amp maximum at 80 VDC, 125 VDC,
and 120 VAC. Auxiliary / Alarm Switch with Dependent Circuit ie: same as circuit
breaker, is supplied from factory with common terminal of auxiliary / alarm switch
connected to line terminal on 120/240 and 240 VAC ratings. Circuit breakers rated
120 VAC 50 amp maximum can be supplied with Auxiliary/Alarm switch common
terminal connected to breaker line terminal. Consult factory for special catalog
number.
11 MAXIMUM APPLICATION RATING
A
B
C
D
K
F
65 DC
3
125 DC
120/240 AC
240 AC
120 AC
277 AC
80 DC
2
M
11
12 AGENCY APPROVAL
A
without approvals
4
5
Available up to 50 amps maximum.
Current ratings 71 - 100 with VDE approvals are available up to two poles
maximum.
Terminal Codes 9 & C are not VDE approved.
Terminal Code 1 available to 60 amps maximum.
Fꢀꢀ
Gꢀ
Jꢀꢀ
UL489ꢀListed,ꢀCSAꢀCertifiedꢀ&ꢀVDEꢀCertified
UL489ꢀListedꢀ&ꢀCSAꢀCertified
6
7
8
9
UL489ꢀListed,ꢀCSAꢀCertifiedꢀ&ꢀTUVꢀCertified
Terminal Codes 2, 4, 5 & C available to 50 amps maximum.
Terminal Codes 3, 6 & 9 available to 100 amps maximum.
10 Terminal Code A available to 100 amps maximum.
11 VDE and TUV approvals require Dual (I-O, ON-OFF) markings on all handles.
12 Barriers supplied on multi-pole units only.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
10 C-Series Circuit Breaker - Sealed Toggle UL Recognized – Ordering Scheme
C M 3 B 0 10 450 1 0 1 C
8
9
10
11
Agency
Approval
1
2
3
4
5
6
7
Terminal
Legend
Plate
Mounting
Bezel/Barrier
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
9
1 SERIES
C
7 CURRENT RATING (AMPERES)
CODE AMPERES
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
1
2 ACTUATOR
M
Sealed Toggle, one per pole
3 POLES
1
One
2
Two
3
Three
3
3
3,4
4 CIRCUIT
F
G
H
Relay Trip (current)
Relay Trip (voltage)
Dual Coil with Shunt Trip
Voltage Coil
Dual Coil with Relay Trip
Voltage Coil
2
A
B
C
D
E
Switch Only (no coil)
9
Series Trip (current)
Series Trip (voltage)
Shunt Trip (current)
Shunt Trip (voltage)
660 60.000
9
670 70.000
9
3
3
3,4
680 80.000
K
9
685 85.000
9
690 90.000
9
695 95.000
9
810 100.00
5 AUXILIARY / ALARM SWITCH
0
2
3
4
without Aux Switch
7
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
CODE AMPERES
A06
6 DC
A32 32 DC
A48 48 DC
A65 65 DC
J12 12 AC
J18 18 AC
J24 24 AC
J48 48 AC
J65
65 AC
A12 12 DC
A18 18 DC
A24 24 DC
K20 120 AC
L40 240 AC
J06
6 AC
6 FREQUENCY & DELAY
2
8 TERMINAL
03
10
11
12
14
16
20
21
22
24
26
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
30
31
32
34
36
42
44
46
52
54
56
DC 50/60Hz Instantaneous
DC 50/60Hz Ultra Short
DC 50/60Hz Short
DC 50/60Hz Medium
DC 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
DC Medium, Hi-Inrush
DC Long, Hi-Inrush
9
11
6
1
2
3
4
5
Stud 10-32
Screw 10-32
Stud 1/4-20
Stud M5 x 0.8
Screw M5 x 0.8
6
7
9
A
C
Stud M6
10
11
10
10
12
11
13
10
0.250 Double Click Connect
7/16” Clip Terminal
Plug-In Stud
7
7
7
7
5/16” Clip Terminal
6
9 LEGEND PLATE
No Legend
7
0
10 MOUNTING / BARRIERS
MOUNTING STYLE
Notes:
1
Actuator Code M: Handle location as viewed from front of breaker:
2 pole - right pole 3 pole - center pole
Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE.
For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current
Code 650. For 55-70 amps, select Current Code 670. For 75-100 amps, select
Current Code 810.
BARRIERS
no
yes
1
A
Standard Hex Nut
Standard Hex Nut (multi-pole units only)
2
11 AGENCY APPROVAL
3
4
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only.
Consult factory for available Dual Coil options, as special catalog number is
required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously
on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip
instantaneously and are rated for intermittent duty only.
C
I
L
UL Recognized & CSA Accepted
UL Recognized & CSA Accepted, UL1500 ignition protection
UL Recognized & CSA Accepted with listed construction
5
Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole
breakers, one auxiliary switch is supplied, mounted in the extreme right pole.
Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20.
Available with Circuit Codes B & D only, and up to 50 amps maximum.
Consult factory for current ratings 71-100, in three pole units, available as special
catalog number only.
6
7
8
9
Terminal Code 1 available to 60 amps maximum.
10 Terminal Codes 2, 4, 5 and C available to 50 amps maximum.
11 Terminal Codes 3, 6 & 9 available to 100 amps maximum.
12 Terminal Code 7 available to 25 amps maximum.
13 Terminal Code A available to 100 amps maximum.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
C-Series Circuit Breaker - Rocker UL Recognized – Ordering Scheme |
11
14 450
C C 3 B 0
1 2 1 D
6
7
8
9
10
Mounting/
Barriers
11
Agency
Approval
1
2
3
4
5
Frequency
& Delay
Current Rating
Terminal
Actuator
Color
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
1 SERIES
C
7 CURRENT RATING (AMPERES)
CODE AMPERES
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
1
2 ACTUATOR
Two Color Visi-Rocker
C
D
E
F
Indicate ON, vertical legend
Indicate ON, horizontal legend
Indicate ON, no legend
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
Indicate OFF, no legend
G
H
Push-To-Reset, Visi-Rocker
N
O
P
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
Indicate OFF, no legend
9
660 60.000
9
Single color
670 70.000
9
J
K
L
Vertical legend
Horizontal legend
No legend
680 80.000
9
685 85.000
9
690 90.000
9
Push-To-Reset, Single color
695 95.000
9
R
U
V
Vertical legend
Horizontal legend
No legend
810 100.00
7
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)
CODE AMPERES
A06
6 DC
A32 32 DC
A48 48 DC
A65 65 DC
J12 12 AC
J18 18 AC
J24 24 AC
J48 48 AC
J65
65 AC
A12 12 DC
A18 18 DC
A24 24 DC
K20 120 AC
L40 240 AC
2
3 POLES
One
1
2
Two
3
Three
J06
6 AC
4
4
4,5
4,5
4 CIRCUIT
F
Relay Trip (Current)
Relay Trip (Voltage)
3
8 TERMINAL
A
B
C
D
E
Switch Only (No Coil)
G
H
10
12
13
1
2
3
4
5
Stud 10-32
6
Stud M6
Series Trip (Current)
Series Trip (Voltage)
Shunt Trip (Current)
Shunt Trip (Voltage)
Dual Coil with Shunt Trip
Voltage Coil
11
12
11
11
Screw 10-32
Stud 1/4-20
7
0.250 Double Quick Connect
7/16” Clip Terminal
Plug-In Stud
4
4
9
A
C
K
Dual Coil with Relay Trip
Voltage Coil
14
Stud M5 x 0.8
Screw M5 x 0.8
5/16” Clip Terminal
6
5 AUXILIARY / ALARM SWITCH
16,17,18
9 ACTUATOR COLOR & LEGEND
Actuator or
0
2
3
4
without Aux Switch
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
Visi-Color Marking:
MarkingColor:
Single Color
Color:
White
Black
Red
I-O ON-OFF Dual/None Rocker/Handle Visi-Rocker
A
C
F
H
K
M
P
R
B
D
G
J
1
2
3
4
5
6
7
8
Black
White
White
White
White
Black
Black
Black
White
n/a
Red
6 FREQUENCY & DELAY
Green
Blue
Green
Blue
Yellow
Gray
Orange
03
10
11
12
14
16
20
21
22
24
26
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
30
DC 50/60Hz Instantaneous
DC 50/60Hz Ultra Short
DC 50/60Hz Short
L
7
31
32
34
36
42
44
46
52
54
56
Yellow
Gray
Orange
N
Q
S
DC 50/60Hz Medium
DC 50/60Hz Long
DC Medium
8
8
8
8
8
8
DC Long
50/60Hz Short, Hi-Inrush
7
1
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium, Hi-Inrush
10 MOUNTING / BARRIERS
50/60Hz Long, Hi-Inrush
STANDARD ROCKER BEZEL
6-32 x 0.195 inches
6-32 x 0.195 inches
ꢀꢀ 6-32ꢀxꢀ0.195ꢀinchesꢀ
ISO M3 x 5mm
BARRIERS
VOLTAGE
<300
DC Short, Hi-Inrush
1
2
3
4
5
6
no
50/60Hz Medium
50/60Hz Long
DC Medium, Hi-Inrush
yes
yesꢀ
no
yes
yesꢀ
<300
19
19
DC Long, Hi-Inrush
≥300
<300
Notes:
ISO M3 x 5mm
<300
1
2
Push-To-Reset actuators have OFF portion of rocker shrouded.
ꢀꢀ ISOꢀM3ꢀxꢀ5mmꢀ
≥300
Multi-pole breakers have all poles identical except when specifying Auxiliary switch
and/or mixed poles, and have one rocker per breaker. Rocker location as viewed from
front panel: 2 pole – left pole; 3 pole – center pole.
ROCKERGUARD BEZEL
6-32 x 0.195 inches
6-32 x 0.195 inches
ꢀꢀ 6-32ꢀxꢀ0.195ꢀinchesꢀ
ISO M3 x 5mm
ISO M3 x 5mm
A
C
E
G
J
no
<300
<300
≥300
<300
<300
≥300
3
ꢀ
Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE
Certificationꢀwhenꢀtiedꢀtoꢀaꢀprotectedꢀpoleꢀ(CircuitꢀCodeꢀB,ꢀC,ꢀDꢀorꢀH.),ꢀForꢀ.02ꢀtoꢀꢀ
30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650.
For 55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit
Codes D,F,H & K available up to 50 amps maximum Current Rating.
Consult factory for available Dual Coil options, as special catalog number is
required. Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously
on line voltage. Dual Coil Voltage Coils require 30VA minimum power to trip
instantaneously and are rated for intermittent duty only.
yes
yesꢀ
no
19
19
4
5
yes
yesꢀ
L
ꢀꢀ ISOꢀM3ꢀxꢀ5mmꢀ
PUSH-TO-RESET BEZEL
6-32 x 0.195 inches
6-32 x 0.195 inches
ꢀꢀ 6-32ꢀxꢀ0.195ꢀinchesꢀ
ISO M3 x 5mm
B
D
F
H
J
M
no
<300
<300
≥300
<300
<300
≥300
yes
yesꢀ
no
19
6
Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole
breakers, one auxiliary switch is supplied, mounted in the extreme right pole. Auxiliary
switch codes 2, 3 & 4 are VDE approved.
ISO M3 x 5mm
ꢀꢀ ISOꢀM3ꢀxꢀ5mmꢀ
yes
yesꢀ
7
8
9
Voltage coils not rated for continuous duty. Available only with delay codes 10 & 20.
Available with Circuit Codes B & D only, and up to 50 amps maximum.
Current Ratings 60-70 are available up to four poles maximum. Ratings 71-100 are
available up to two poles maximum.
19
10 Terminal Code 1 available to 60 amps maximum.
11 AGENCY APPROVAL
UL Recognized & CSA Accepted
11 Terminal Codes 2,4,5 & C available to 50 amps maximum.
12 Terminal Codes 3,6 & 9 available to 100 amps maximum.
13 Terminal Code 7 available to 25 amps maximum.
C
Dꢀꢀ VDEꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted
Eꢀꢀ TUVꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted
14 Terminal Code A available to 100 amps maximum.
15 Terminal Codes 7, 9 & C are not VDE approved.
Hꢀꢀ UL489ꢀConstruction:ꢀVDEꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted
16 Color shown is visi and legend with remainder of rocker black
17 Legend on Push-to-reset bezel/shroud is white when single color rocker is ordered.
Dual = ON-OFF/I-O legend with actuator codes C - G, and J, K, N, O, R, & U. None
= no legend with actuator codes H, L, P, V. Rockerguard available with actuator
codes C - L. Push-to-reset available with actuator codes N, O, P, R, U, V.
18 VDE/TUV approval requires Dual (I-O, ON-OFF) or I-O markings on rocker.
19 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 - 4 poles only
and limited to AC Delays. “General Purpose amps” not rated for “full load amps” or
to be used in applications with a motor.
I
UL Recognized STD 1077, UL Recognized 1500 (ignition protected),
& CSA Accepted
L
Rꢀ
UL489 Construction: UL Recognized & CSA Accepted
UL489ꢀConstruction:ꢀTUVꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
12 C-Series Circuit Breaker - Rocker UL Listed – Ordering Scheme
C C 3 B 0 14 450 1 2 A K G
8
9
10
Mounting/
Barriers
11
12
1
2
3
4
5
6
7
Terminal
Actuator
Color
Max. App. Agency
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
Rating
Approval
4
7 CURRENT RATING (AMPERES)
1 SERIES
C
CODE AMPERES
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
660 60.000
670 70.000
680 80.000
685 85.000
690 90.000
695 95.000
810 100.00
1
2 ACTUATOR
Two Color Visi-Rocker
Single color
C
D
F
Indicate ON, vertical legend
Indicate ON, horizontal legend
Indicate OFF, vertical legend
J
K
Vertical legend
Horizontal legend
G
Indicate OFF, horizontal legend
ROCKER STYLE DESCRIPTIONS
INDICATE "ON"
INDICATE "OFF"
CODE "F"
SINGLE COLOR
CODE "J"
CODE "C"
LINE
INDICATE
COLOR
LINE
LINE
LOCATION
CODE "D"
CODE "G"
CODE "K"
8 TERMINAL
5
7
1
2
Stud 10-32
6
9
A
C
Stud M6
7/16” Clip Terminal
Plug-In Stud
6
7,8
7,8
6,8
Screw 10-32 with saddle
& washer clamps
Stud 1/4-20
7
6
6
3
4
5
5/16” Clip Terminal
LINE
LINE
LINE
Stud M5 x 0.8
Screw M5 x 0.8 with saddle
& washer clamps
1
3 POLES
One
1
2
Two
3
Three
11
9 ACTUATOR COLOR & LEGEND
Actuator or
4 CIRCUIT
Series Trip (current)
Visi-Color
Marking:
Marking Color:
Single Color
Rocker/Handle
Black
B
10
Color:
White
Black
Red
ON-OFF Dual
Visi-Rocker
White
n/a
B
D
G
J
1
2
3
4
5
6
7
8
2
5 AUXILIARY / ALARM SWITCH
White
0
2
3
4
without Aux Switch
White
Red
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
Green
Blue
White
Green
Blue
L
White
Yellow
Gray
Orange
N
Q
S
Black
Yellow
Gray
Black
Black
Orange
6 FREQUENCY & DELAY
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
8
8
8
8
12
42 50/60Hz Short, Hi-Inrush
10 MOUNTING / BARRIERS
Standard Rocker Bezel
13
44 50/60Hz Medium, Hi-Inrush
BARRIERS
46 50/60Hz Long, Hi-Inrush
Threaded Insert, 2 per pole
6-32 X 0.195 inches
ISO M3 x 5mm
Rockerguard Bezel
Threaded Insert, 2 per pole
6-32 x 0.195 inches
ISO M3 x 5mm
52 DC Short, Hi-Inrush
A
C
yes
yes
8
54 DC Medium, Hi-Inrush
56 DC Long, Hi-Inrush
B
D
yes
yes
Notes:
1
Multi-pole breakers have all breakers identical except when specifying Auxiliary
switch and/or mixed poles, and have one rocker per breaker.
On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right
pole.
11 MAXIMUM APPLICATION RATING
2
A
B
C
D
F
K
M
65 DC
125 DC
120/240 AC
240 AC
277 AC
120 AC
80 DC
3
4
5
6
7
8
9
Available up to 50 amps maximum.
14
Current ratings 71 - 100 with VDE approvals are available up to two poles maximum.
Terminal Code 1 available to 60 amps maximum.
Terminal Codes 2, 4, 5 & C available to 50 amps maximum.
Terminal Codes 3, 6, 9 & A available to 100 amps maximum.
Terminal Codes 9 & C are not VDE approved.
Color shown is visi and legend with remainder of rocker black
10 Dual = ON-OFF/I-O legend on actuator.
11 VDE and TUV approval requires Dual (I-O, ON-OFF) markings on rocker.
12 Rockerguard available with all actuator codes.
12 AGENCY APPROVAL
13 Barriers supplied on multi-pole units only.
A
Fꢀꢀ
G
without approvals
ULꢀ489ꢀListed,ꢀCSAꢀCertified,ꢀ&ꢀVDEꢀCertified
ULꢀ489ꢀListedꢀ&ꢀCSAꢀCertified
14 2 & 3 pole circuit breakers required for 120/240 AC rating.
Jꢀꢀ
UL489ꢀListed,ꢀCSAꢀCertifiedꢀ&ꢀTUVꢀCertified
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
C-Series Circuit Breaker - Flat Rocker UL Recognized – Ordering Scheme |
13
C 1 2 B 0 10 450 1 2 1 E
8
9
10
Mounting/
Barriers
11
Agency
Approval
1
2
3
4
5
6
7
Terminal
Actuator
Color
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
9
1 SERIES
C
7 CURRENT RATING (AMPERES)
CODE AMPERES
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
1
2 ACTUATOR
Two Color Visi-Rocker
1
Indicate OFF,
vertical legend
Indicate OFF,
horizontal legend
2
Single color
3
4
Vertical legend
Horizontal legend
Push-To-Reset, Visi-Rocker
5
Indicate OFF,
vertical legend
Indicate OFF,
9
660 60.000
9
670 70.000
6
9
680 80.000
horizontal legend
9
685 85.000
Push-To-Reset , Single color
9
690 90.000
7
8
Vertical legend
9
695 95.000
Horizontal legend
9
810 100.00
7
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)
2
3 POLES
One
CODE AMPERES
1
2
Two
3
Three
A06
6 DC
A32 32 DC
A48 48 DC
A65 65 DC
J12 12 AC
J18 18 AC
J24 24 AC
J48 48 AC
J65
65 AC
A12 12 DC
A18 18 DC
A24 24 DC
K20 120 AC
L40 240 AC
4
4
4,5
4,5
4 CIRCUIT
F
Relay Trip (Current)
Relay Trip (Voltage)
J06
6 AC
3
A
B
C
D
E
Switch Only (No Coil)
G
H
Series Trip (Current)
Series Trip (Voltage)
Shunt Trip (Current)
Shunt Trip (Voltage)
Dual Coil with Shunt Trip
Voltage Coil
8 TERMINAL
4
4
K
Dual Coil with Relay Trip
Voltage Coil
10
12
1
2
3
4
5
Stud 10-32
6
Stud M6
11
12
11
11
13
15
14
15
Screw 10-32
Stud 1/4-20
7
0.250 Double Quick Connect
7/16” Clip Terminal
Plug-In Stud
9
Stud M5 x 0.8
Screw M5 x 0.8
A
C
6
5 AUXILIARY / ALARM SWITCH
5/16” Clip Terminal
0
2
3
4
without Aux Switch
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
16,17,18
9 ACTUATOR COLOR & LEGEND
Actuator or
Visi-Color Marking:
MarkingColor:
Single Color
Color:
White
Black
Red
I-O ON-OFF Dual/None Rocker/Handle Visi-Rocker
A
C
F
B
D
G
J
1
2
3
4
5
6
7
8
Black
White
White
White
White
Black
Black
Black
White
n/a
6 FREQUENCY & DELAY
03
10
11
12
14
16
20
21
22
24
26
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
30
DC 50/60Hz Instantaneous
DC 50/60Hz Ultra Short
DC 50/60Hz Short
7
Red
31
32
34
36
42
44
46
52
54
56
Green
Blue
H
K
M
P
R
Green
Blue
L
DC 50/60Hz Medium
DC 50/60Hz Long
Yellow
Gray
N
Q
S
Yellow
Gray
Orange
DC Medium
DC Long
8
8
8
8
8
8
50/60Hz Short, Hi-Inrush
7
Orange
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC Short, Hi-Inrush
1
10 MOUNTING / BARRIERS
50/60Hz Medium
50/60Hz Long
DC Medium, Hi-Inrush
STANDARD ROCKER BEZEL
6-32 x 0.195 inches
6-32 x 0.195 inches
ꢀꢀ 6-32ꢀxꢀ0.195ꢀinchesꢀ
ISO M3 x 5mm
BARRIERS
no
yes
yesꢀ
no
yes
yesꢀ
VOLTAGE
<300
DC Long, Hi-Inrush
1
2
3
4
5
6
<300
Notes:
19
19
≥300
1
2
Push-to-reset actuators have OFF portion of rocker shrouded.
Multi-pole breakers have all poles identical except when specifying Auxiliary switch
and/or mixed poles, and have one rocker per breaker. Rocker location as viewed
from front panel: 2 pole – left pole; 3 pole – center pole.
<300
ISO M3 x 5mm
<300
ꢀꢀ ISOꢀM3ꢀxꢀ5mmꢀ
≥300
3
ꢀ
Switch Only circuits, rated up to 50 amps and 3 poles, and only available with VDE
Certificationꢀwhenꢀtiedꢀtoꢀaꢀprotectedꢀpoleꢀ(CircuitꢀCodeꢀB,ꢀC,ꢀDꢀorꢀH.).ꢀForꢀ.02ꢀtoꢀ30ꢀꢀ
amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. For
55-70 amps, select Current Code 670. For 75-100 amps, select Current Code 810.
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit
Codes D,F,H & K available up to 50 amps maximum Current Rating.
Consult factory for available Dual Coil options, as special catalog number is required.
Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line
voltage. Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously
and are rated for intermittent duty only.
RECESSED OFF ROCKER
6-32 x 0.195 inches
6-32 x 0.195 inches
6-32ꢀxꢀ0.195ꢀinchesꢀꢀ
ISO M3 x 5mm
7
8
no
<300
<300
≥300
<300
<300
≥300
yes
yesꢀꢀ
no
4
5
9ꢀꢀ
A
C
E ꢀ
ISO M3 x 5mm
yes
yesꢀꢀ
ISOꢀM3ꢀxꢀ5mmꢀꢀ
PUSH-TO-RESET BEZEL
6-32 x 0.195 inches
6-32 x 0.195 inches
6
Auxiliary Switch available with Series Trip and Switch Only circuits. On multi-pole
breakers, one auxiliary switch is supplied, mounted in the extreme right pole. Auxilary
switch codes 2, 3 & 4 are VDE approved.
B
D
F
H
J
no
<300
<300
≥300
<300
<300
≥300
yes
yesꢀ
no
19
ꢀꢀ 6-32ꢀxꢀ0.195ꢀinchesꢀ
ISO M3 x 5mm
ISO M3 x 5mm
ꢀꢀ ISOꢀM3ꢀxꢀ5mmꢀ
7
8
9
Voltage coils not rated for continuous duty. Available only with delay codes 10 and 20.
Available with Circuit Codes B & D only, and up to 50 amps maximum.
Current ratings 60-70 are available up to four poles maximum. Current ratings 71 -
100 are available up to two poles maximum.
yes
yesꢀ
19
M
10 Terminal Code 1 available to 60 amps maximum.
11 Terminal Codes 2,4,5 & C available to 50 amps maximum.
12 Terminal Codes 3,6 & 9 available to 100 amps maximum.
13 Terminal Code 7 available to 25 amps maximum.
11 AGENCY APPROVAL
UL Recognized & CSA Accepted
14 Terminal Code A available to 100 amps maximum.
C
15 Terminal Codes 7, 9 & C are not VDE approved.
Eꢀꢀ TUVꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted
16 Color shown is visi & legend with remainder of rocker black. Dual = ON-OFF/I-O legend.
17 Legend on Push-to-reset bezel/shroud is white with single color actuator codes 7 &
8. Legend on Push-to-reset bezel/shroud matches visi-color of rocker with actuator
codes 5 & 6.
I
UL Recognized STD 1077, UL Recognized 1500 (ignition protected),
& CSA Accepted
UL489 Construction: UL Recognized & CSA Accepted
UL489ꢀConstruction:ꢀTUVꢀCertified,ꢀULꢀRecognizedꢀ&ꢀCSAꢀAccepted
L
18 VDE/TUV approval requires Dual (I-O, ON-OFF) or I-O markings on rocker.
19 VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 & 3 poles only and
limited to AC Delays. “General Purpose amps” not rated for “full load amps” or to be
used in applications with a motor.
20 Recessed “OFF SIDE” available with actuator codes 1,2,3&4. Legends on rocker are
available in ink stamping only.
Rꢀ
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
14 C-Series Circuit Breaker - Flat Rocker UL Listed – Ordering Scheme
C 1 2 B 0 14 450 1 2 A K G
8
9
10
Mounting/
Barriers
11
12
1
2
3
4
5
6
7
Terminal
Actuator
Color
Max. App. Agency
Series
Actuator
Poles
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
Rating
Approval
5
7 CURRENT RATING (AMPERES)
1 SERIES
C
CODE AMPERES
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
660 60.000
670 70.000
680 80.000
685 85.000
690 90.000
695 95.000
810 100.00
1
2 ACTUATOR
Two Color Visi-Rocker
Push-To-Reset, Visi-Rocker
1
2
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
5
6
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
Single color
3
4
Push-To-Reset , Single color
Vertical legend
Horizontal legend
7
8
Vertical legend
Horizontal legend
8 TERMINAL
6
8
8,9
8
1
2
3
4
5
Stud 10-32
6
9
A
C
Stud M6
7/16” Clip Terminal
Plug-In Stud
7
8
7
7
Screw 10-32
Stud 1/4-20
Stud M5 x 0.8
7,9
5/16” Clip Terminal
Screw M5 x 0.8
10
9 ACTUATOR COLOR & LEGEND
2
3 POLES
One
Actuator or
1
2
Two
3
Three
Visi-Color
Marking:
Marking Color:
Single Color
Rocker/Handle
Black
11,12
Color:
White
Black
Red
ON-OFF Dual
Visi-Rocker
White
n/a
4 CIRCUIT
Series Trip (current)
B
D
G
J
1
2
3
4
5
6
7
8
B
White
White
Red
Green
Blue
White
Green
Blue
3
5 AUXILIARY / ALARM SWITCH
L
White
Yellow
Gray
Orange
N
Q
S
Black
Yellow
Gray
0
2
3
4
without Aux Switch
Black
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.139 Solder Lug
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6
8
9
S.P.S.T., 0.139 Solder Lug
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
Black
Orange
10 MOUNTING / BARRIERS
15
STANDARD ROCKER BEZEL
Threaded Insert, 2 per pole
6-32 X 0.195 inches
BARRIERS
6 FREQUENCY & DELAY
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
4
4
4
4
4
4
A
C
yes
yes
42 50/60Hz Short, Hi-Inrush
44 50/60Hz Medium, Hi-Inrush
46 50/60Hz Long, Hi-Inrush
52 DC Short, Hi-Inrush
54 DC Medium, Hi-Inrush
56 DC Long, Hi-Inrush
ISO M3 x 5mm
14
RECESSED OFF ROCKER
Threaded Insert, 2 per pole
6-32 x 0.195 inches
ISO M3 x 5mm
E
F
yes
yes
13
PUSH-TO-RESET BEZEL
Threaded Insert, 2 per pole
6-32 x 0.195 inches
ISO M3 x 5mm
B
D
yes
yes
Notes:
1
2
Push-to-reset actuators have OFF portion of rocker shrouded.
Multi-pole breakers have all breakers identical except when specifying Auxiliary
switch and/or mixed poles, and have one rocker per breaker.
On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme
right pole.
11 MAXIMUM APPLICATION RATING
3
A
B
C
D
F
K
M
65 DC
4
5
6
7
8
9
Available up to 50 amps maximum.
125 DC
120/240 AC
240 AC
277 AC
120 AC
80 DC
16
Current ratings 71 - 100 with VDE approvals are available up to two poles maximum.
Terminal Code 1 available to 60 amps maximum.
Terminal Codes 2, 4, 5 & C available to 50 amps maximum.
Terminal Codes 3, 6, 9 & A available to 100 amps maximum.
Terminal Codes 9 & C are not VDE approved.
10 Color shown is visi and legend with remainder of rocker black
11 Dual = ON-OFF/I-O legend on actuator.
12 TUV approval requires Dual (I-O, ON-OFF) markings on rocker.
13 Legend on push-to-reset bezel/shroud is white when single color rocker is ordered.
Legend on push-to-reset bezel/shroud matches visi-color of rocker with actuator
codes 5 & 6.
14 Recessed “OFF-SIDE” available with actuator codes 1, 2, 3, & 4. Legends on rocker
are available in ink stamping only.
12
12 AGENCY APPROVAL
A
without approvals
G
Jꢀꢀ
ULꢀ489ꢀListedꢀ&ꢀCSAꢀCertified
UL489ꢀListed,ꢀCSAꢀCertifiedꢀ&ꢀTUVꢀCertified
15 Barriers supplied on multi-pole units only.
16 2 & 3 pole circuit breakers required for 120/240 AC rating.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
C-Series Circuit Breaker - Handle – Circuit & Terminal Diagrams |
15
Circuit & Terminal Diagrams: in. [mm]
.960 [24.38]
.311 DIA [Ø7.90]
.558 [14.17]
Notes:
1
2
3
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Available on Series Trip and Switch Only Circuits when called for on multi-pole units.
Onlyꢀoneꢀauxiliaryꢀswitchꢀisꢀnormallyꢀsupplied,ꢀasꢀviewedꢀinꢀmulit-poleꢀidentificationꢀscheme.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
16 C-Series Circuit Breaker - Handle – Circuit & Terminal Diagrams
Circuit & Terminal Diagrams: in. [mm]
Notes:
1
2
3
4
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Schematic shown represents current trip circuits.
Available only as special catalog number.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
C-Series Circuit Breaker - Handle – Dimensional Specifications |
17
Dimensional Specifications: in. [mm]
Notes:
1
2
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
18 C-Series Circuit Breaker - Handleguard – Dimensional Specifications
Dimensional Specifications: in. [mm]
Notes:
1
2
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
C-Series Circuit Breaker - Arc Chute Barrier UL Recognized/Listed – Dimensional Specifications |
19
Dimensional Specifications: in. [mm]
Notes:
1
Onlyꢀ1-poleꢀandꢀ3-poleꢀconfigurationsꢀshown.ꢀArcꢀchuteꢀ(withoutꢀbarrier)ꢀandꢀarcꢀchuteꢀꢀ
barrier also available for 2-pole construction.
2
3
Dimensions apply to all variations shown.
Notice that line and load terminal orientation for indicate on and indicate off rocker
circuit breakers are opposite.
4
ꢀ
5
6
7
Screw type terminals shown for Rocker style (CF1, C11, etc) circuit breakers. For
otherꢀterminalꢀconfigurationsꢀseeꢀcircuitꢀandꢀterminalꢀdiagrams.
All dimensions are in inches [millimeters].
Toleranceꢀ±ꢀ.020ꢀunlessꢀotherwiseꢀspecified.
Must be ordered under a special catalog number.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
20 C-Series Circuit Breaker - Parallel Pole – Dimensional Specifications
Dimensional Specifications: in. [mm]
Notes:
1
2
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
C-Series Circuit Breaker - Sealed Toggle – Dimensional Specifications |
21
Dimensional Specifications: in. [mm]
Notes:
1
2
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
22 C-Series Circuit Breaker - Rocker – Circuit & Terminal Diagrams
Circuit & Terminal Diagrams: in. [mm]
Notes:
1
2
3
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Schematic shown represents current trip circuit.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
C-Series Circuit Breaker - Rocker – Dimensional Specifications |
23
Dimensional Specifications: in. [mm]
Notes:
1
2
3
4
Dimensions apply to all variations shown. Notice that circuit breaker line and load terminal orientation on indicate OFF is opposite of indicate ON.
For pole orientation with horizontal legend, rotate front view clockwise 90°.
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
24 C-Series Circuit Breaker - Flat Rocker – Dimensional Specifications
Dimensional Specifications: in. [mm]
Notes:
1
2
3
For pole orientation with horizontal legend, rotate front view clockwise 90°.
All dimensions are in inches [millimeters].
Toleranceꢀ±.020ꢀ[.51]ꢀunlessꢀotherwiseꢀspecified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
Reps & Contact
25
Authorized Sales Representatives
Click on the group name on the map below to find your local representative or visit
www.carlingtech.com/findarep.
Matera
W. Canada
Matera
E. Canada
MIDWEST
DM
MichigaNn ORTHERN
TEMCO Northwest
Hanna Lind Ltd.
Melody
Sierra
Emery
LD. Allen
Norris
«
DM Assoc
Bridge Marketing
Signal
East
Pacent
TSI North
Omega Limited
Dy-tronix Inc.
DM
Assoc
TSI
Luscombe
Engineering
WEST
Enterprises
Pinnacle Marketing
ProRep
Sunbelt Components
SOUTHEAST
Matrix
DM Mexico
South America
Mexico
Solutions
LATIN AMERICA
Europe
Middle East
Africa
Asia-Pacific
Oceania
Americas
About Carling
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches
and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power
distribution systems. With four ISO registered manufacturing facilities and technical sales offices worldwide,
Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical
components, they engineer powerful solutions! To learn more about Carling please visit
www.carlingtech.com/company-profile.
To view all of Carling’s environmental, quality, health & safety certifications please visit
www.carlingtech.com/environmental-certifications
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Phone: 860.793.9281 Fax: 860.793.9231
@
Email: sales carlingtech.com
@
Northern Region Sales Office: nrsm carlingtech.com
@
Southeast Region Sales Office: sersm carlingtech.com
@
Midwest Region Sales Office: mrsm carlingtech.com
@
West Region Sales Office: wrsm carlingtech.com
@
Latin America Sales Office: larsm carlingtech.com
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacific Ltd.,
Kowloon, Hong Kong
Phone: Int + 852-2737-2277 Fax: Int + 852-2736-9332
@
Email: sales carlingtech.com.hk
@
Shenzhen, China: shenzhen carlingtech.com
@
Shanghai, China: shanghai carlingtech.com
@
Pune, India: india carlingtech.com
@
Kaohsiung, Taiwan: taiwan carlingtech.com
@
Yokohama, Japan: japan carlingtech.com
|
|
Europe Middle East Africa Headquarters
Carling Technologies LTD
4 Airport Business Park, Exeter Airport,
Clyst Honiton, Exeter, Devon, EX5 2UL, UK
Phone: Int + 44 1392.364422 Fax: Int + 44 1392.364477
@
Email: ltd.sales carlingtech.com
@
Germany: gmbh carlingtech.com
@
France: sas carlingtech.com
www.carlingtech.com
REV_07_2016